Fire Batt

Quick Quote

Call Benn Larkin Anand Raghavan Ben Tan Krishna Kumar Anand Raghavan Our USA Office on

Fire Batt

Up to 60 minute walls

Barrier Service Integrity Insulation
Single Layer (50mm) Cable Ladder (340mm wide by 100mm high max.) 60 minutes 60 minutes
Cables up to 26mm diameter 60 minutes N/A
Steel pipes up to 60mm diameter 60 minutes 30 minutes
PVC pipes up to 110mm diameter 60 minutes N/A
Steel ducts (445mm wide by 455mm high max.) 60 minutes N/A

 

Up to 120 minute walls

Barrier Service Integrity Insulation
Single Layer (50mm) Cable Ladder (340mm wide by 100mm high max.) 120 minutes 60 minutes
Cables up to 26mm diameter 120 minutes N/A
Steel pipes up to 60mm diameter 120 minutes 30 minutes
PVC pipes up to 110mm diameter 120 minutes N/A
Steel ducts (445mm wide by 445mm high max.) 120 minutes N/A
Double Layer (100mm) 2 x 50mm Cable Ladder (340mm wide by 100mm high max.) 120 minutes 60 minutes
Cables up to 26mm diameter 120 minutes 60 minutes
Steel pipes up to 60mm diameter 120 minutes 30 minutes
PVC pipes up to 110mm diameter 60 minutes N/A
Steel ducts (445mm wide by 445mm high max.) 120 minutes N/A

 

Up to 120 minute floors

Barrier Service Integrity Insulation
Double Layer (100mm) Cable Ladder (340mm wide by 100mm high max.) 120 minutes 60 minutes
Cables up to 20mm diameter 120 minutes 60 minutes

 

Up to 240 minute walls

Barrier Service Integrity Insulation
Single Layer (50mm) Cable Ladder (340mm wide by 100mm high max.) 240 minutes N/A
Cables up to 20mm diameter 240 minutes N/A
Double Layer (100mm) Cable Ladder (340mm wide by 100mm high max.) 240 minutes 60 minutes
2 x 50mm Cables up to 20mm diameter 240 minutes 60 minutes

 

 